電纜隧道細水霧滅火系統(tǒng)典型實體火災試驗
發(fā)布時間:2019-02-17 17:11
【摘要】:本文結合工程案例,以材質為聚乙烯、阻燃級別為C類阻燃的0.6/1k V干式交聯(lián)電纜為試驗對象,采用全尺寸實體火災試驗的方法,研究細水霧滅火系統(tǒng)撲救典型電纜隧道火災的有效性。試驗表明細水霧滅火系統(tǒng)對典型電纜隧道火災的延燒可起到有效的控滅火作用。
[Abstract]:In this paper, taking 0.6 / 1kV dry crosslinked cable with polyethylene as material and class C flame-retardant as test object, the method of full-scale solid fire test is adopted. The effectiveness of water mist fire extinguishing system for typical cable tunnel fire fighting is studied. The test results show that the water mist fire extinguishing system can effectively control the fire of typical cable tunnel fire.
【作者單位】: 北京市公安消防總隊防火監(jiān)督部;
【分類號】:U458;U459.9
本文編號:2425396
[Abstract]:In this paper, taking 0.6 / 1kV dry crosslinked cable with polyethylene as material and class C flame-retardant as test object, the method of full-scale solid fire test is adopted. The effectiveness of water mist fire extinguishing system for typical cable tunnel fire fighting is studied. The test results show that the water mist fire extinguishing system can effectively control the fire of typical cable tunnel fire.
【作者單位】: 北京市公安消防總隊防火監(jiān)督部;
【分類號】:U458;U459.9
【相似文獻】
相關期刊論文 前1條
1 陳震;姚斌;王文偉;張笑男;;隧道型細水霧滅火系統(tǒng)在公路隧道的設計與應用[J];中國安全生產科學技術;2013年07期
相關會議論文 前2條
1 沈賀坤;趙成剛;;細水霧抑制油漆火災效果研究[A];2014中國消防協(xié)會科學技術年會論文集[C];2014年
2 陳震;;隧道型細水霧滅火系統(tǒng)在公路隧道的設計與應用[A];2013中國消防協(xié)會科學技術年會論文集[C];2013年
,本文編號:2425396
本文鏈接:http://www.sikaile.net/kejilunwen/jiaotonggongchenglunwen/2425396.html