冷凍水流量和溫度對(duì)基于混合工質(zhì)的雙溫冷水機(jī)組性能影響
發(fā)布時(shí)間:2018-06-20 23:01
本文選題:非共沸工質(zhì) + 變流量; 參考:《制冷學(xué)報(bào)》2015年06期
【摘要】:為研究冷凍水流量與溫度變化對(duì)基于大滑移溫度非共沸工質(zhì)雙溫冷水機(jī)組性能的影響規(guī)律,本文在大滑移溫度非共沸工質(zhì)的雙溫冷水機(jī)組實(shí)驗(yàn)臺(tái)進(jìn)行了多組實(shí)驗(yàn)研究。實(shí)驗(yàn)分別研究了非共沸工質(zhì)R32/R236fa在不同質(zhì)量組分比例(0.4∶0.6,0.5∶0.5,0.6∶0.4)下,冷凍水流量由0.25 m~3/h增大到0.45 m~3/h,以及高溫冷凍水溫度變化時(shí),冷水機(jī)組性能的變化情況。實(shí)驗(yàn)結(jié)果表明,在冷卻水進(jìn)出口溫度為32℃與37℃,高、低溫冷凍水溫度分別為7℃,16℃時(shí),不同冷凍水流量下冷水機(jī)組的制冷效率(COP)最大為4.17,最小COP為3.27。此外,高溫冷凍水溫度變化對(duì)冷水機(jī)組COP存在明顯影響。實(shí)驗(yàn)為大滑移溫度的雙溫冷水機(jī)組的應(yīng)用提出了數(shù)據(jù)基礎(chǔ)。
[Abstract]:In order to study the effect of chilled water flow and temperature change on the performance of double-temperature chiller based on large slip temperature non-azeotropic refrigerant, a multi-group experiment was carried out on a double-temperature chiller with large slip temperature and non-azeotropic working fluid. The performance changes of chillers with non-azeotropic working fluid R32 / R236fa at different mass ratios of 0.4: 0.6: 0.5: 0.5: 0.6: 0.4) were studied. The chilled water flow rate increased from 0.25 mm3 / h to 0.45 mm3 / h, as well as the change of high temperature chilled water temperature. The experimental results show that when the inlet and outlet temperatures of cooling water are 32 鈩,
本文編號(hào):2046015
本文鏈接:http://www.sikaile.net/jingjilunwen/jianzhujingjilunwen/2046015.html