地源熱泵系統(tǒng)運(yùn)行換熱區(qū)內(nèi)外地溫場變化特征分析
發(fā)布時(shí)間:2018-01-13 13:11
本文關(guān)鍵詞:地源熱泵系統(tǒng)運(yùn)行換熱區(qū)內(nèi)外地溫場變化特征分析 出處:《太陽能學(xué)報(bào)》2017年10期 論文類型:期刊論文
更多相關(guān)文章: 地源熱泵 地溫場 熱影響半徑 變化幅度
【摘要】:基于上海某高校綜合研究中心地埋管地源熱泵工程,對(duì)地源熱泵系統(tǒng)穩(wěn)定運(yùn)行3 a地埋管換熱區(qū)內(nèi)外地溫場進(jìn)行實(shí)際監(jiān)測(cè),并對(duì)3 a間換熱區(qū)內(nèi)外地溫場變化特征進(jìn)行深入分析。分析結(jié)果表明:系統(tǒng)穩(wěn)定運(yùn)行3 a,換熱區(qū)內(nèi)外地溫受地埋管換熱器取放熱影響呈波狀變化,并且地溫變化相對(duì)于環(huán)境溫度的變化存在一定的滯后性,換熱區(qū)中心區(qū)域約滯后3個(gè)月;隨著深度的增大地溫變化幅度有逐步減小趨勢(shì);實(shí)驗(yàn)場地源熱泵系統(tǒng)持續(xù)運(yùn)行3 a地埋管換熱對(duì)地溫的影響半徑半徑為6.0~9.0 m;實(shí)驗(yàn)場在夏季空調(diào)使用高峰采用了地表水地源熱泵系統(tǒng)進(jìn)行調(diào)峰,系統(tǒng)持續(xù)運(yùn)行3 a地埋管換熱器取放熱基本平衡,未造成地層熱堆積現(xiàn)象,運(yùn)行效果較好。
[Abstract]:Based on the ground ground source heat pump (GSHP) project of a comprehensive research center of a university in Shanghai, the ground source heat pump (GSHP) system has been operated steadily for 3 years and the ground temperature field in and out of the underground heat exchange area has been monitored. The variation characteristics of geothermal field in and out of the heat transfer zone are analyzed in depth. The results show that the system runs steadily for 3 years, and the ground temperature inside and outside the heat transfer zone is wave-shaped under the influence of the exothermic effect of the buried tube heat exchanger. Compared with the change of ambient temperature, the variation of ground temperature has some lag, and the central region of heat transfer region is delayed for about 3 months. With the increase of depth, the range of variation of ground temperature has a tendency to decrease gradually. The influence radius of ground source heat pump system on ground temperature for 3 years is 6.0 ~ 9.0 m. The ground water ground-source heat pump system was used to adjust the peak value of air conditioning in summer. The system operated continuously for 3 years and basically balanced the heat release of the ground heat exchanger, which did not cause the formation heat accumulation phenomenon, and the operation effect was better than that of the ground water ground source heat pump system.
【作者單位】: 同濟(jì)大學(xué)土木工程學(xué)院;上海市地礦工程勘察院;
【分類號(hào)】:TU83
【正文快照】: 0引言地埋管換熱器作為地埋管地源熱泵系統(tǒng)的一個(gè)重要組成部分,對(duì)于地埋管地源熱泵系統(tǒng)可靠運(yùn)行起著至關(guān)重要的作用[1]。地埋管換熱器利用地下土壤溫度相對(duì)穩(wěn)定的特性,通過與地下土壤進(jìn)行熱交換對(duì)建筑物制冷和供暖。因此,地源熱泵系統(tǒng)運(yùn)行期間,地埋管換熱區(qū)地溫場的變化特征對(duì)
【相似文獻(xiàn)】
相關(guān)期刊論文 前4條
1 趙靜;閆振鵬;邵景力;崔亞莉;劉新號(hào);田良河;;區(qū)域流場條件下抽灌模式對(duì)采能區(qū)地溫場的影響[J];湖南科技大學(xué)學(xué)報(bào)(自然科學(xué)版);2009年02期
2 瞿成松;曹袁;徐丹;;上海新江灣地區(qū)淺層地溫場初步分析[J];工程建設(shè)與設(shè)計(jì);2013年05期
3 劉爭平;;多年凍土區(qū)地溫測(cè)試關(guān)鍵技術(shù)研究[J];鐵道工程學(xué)報(bào);2009年02期
4 馬輝,吳亞平,郭春香,馬巍;凍土區(qū)寒季灌樁對(duì)地溫場的影響分析[J];蘭州交通大學(xué)學(xué)報(bào);2005年03期
,本文編號(hào):1418981
本文鏈接:http://www.sikaile.net/jianzhugongchenglunwen/1418981.html
最近更新
教材專著